<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>压力变送器技术文章 - 金湖凯铭仪表</title>
	<atom:link href="https://www.zhanfengdesign.com/category/article/ylyb-article/ylbsq-article/feed/" rel="self" type="application/rss+xml" />
	<link>https://www.zhanfengdesign.com/category/article/ylyb-article/ylbsq-article/</link>
	<description>流量&#124;液位&#124;温度&#124;压力</description>
	<lastBuildDate>Fri, 24 Jul 2026 08:05:48 +0000</lastBuildDate>
	<language>zh-Hans</language>
	<sy:updatePeriod>
	hourly	</sy:updatePeriod>
	<sy:updateFrequency>
	1	</sy:updateFrequency>
	<generator>https://wordpress.org/?v=7.1.3</generator>

<image>
	<url>https://www.zhanfengdesign.com/wp-content/uploads/2026/05/elementor/thumbs/微信图片_20250805143107_120_3-rmwn996852eavbnmbpepzofwfik8mes0k2lm3lqvvs.png</url>
	<title>压力变送器技术文章 - 金湖凯铭仪表</title>
	<link>https://www.zhanfengdesign.com/category/article/ylyb-article/ylbsq-article/</link>
	<width>32</width>
	<height>32</height>
</image> 
	<item>
		<title>供水管网防堵塞不锈钢压力变送器选型技巧</title>
		<link>https://www.zhanfengdesign.com/9552/</link>
					<comments>https://www.zhanfengdesign.com/9552/#respond</comments>
		
		<dc:creator><![CDATA[jingangxiaohulu3wa]]></dc:creator>
		<pubDate>Fri, 24 Jul 2026 08:05:20 +0000</pubDate>
				<category><![CDATA[压力变送器技术文章]]></category>
		<category><![CDATA[技术文章]]></category>
		<category><![CDATA[压力仪表]]></category>
		<category><![CDATA[压力变送器]]></category>
		<guid isPermaLink="false">https://www.zhanfengdesign.com/?p=9552</guid>

					<description><![CDATA[<p>市政供水管网水中含有泥沙、铁锈、杂质，极 [&#8230;]</p>
<p><a href="https://www.zhanfengdesign.com/9552/">供水管网防堵塞不锈钢压力变送器选型技巧</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></description>
										<content:encoded><![CDATA[
<p class="wp-block-paragraph">市政供水管网水中含有泥沙、铁锈、杂质，极易堵塞取压部位，影响压力采集稳定，<a href="https://www.zhanfengdesign.com/ylbsq/">压力变送器</a>可实时监测管网水压，保障供水调度稳定。</p>



<p class="wp-block-paragraph">一、过流结构防堵塞选型<br>优先选用大平面平滑膜片结构，无凹陷死角，泥沙杂质不易堆积；避免小孔径引压直连款式。针对老旧管网杂质多的工况，可搭配一体式隔离膜片，阻挡铁锈、颗粒物侵入内部传感腔。<br>取压接口采用大通径螺纹，减少杂物卡堵概率，便于后期冲洗疏通。</p>



<p class="wp-block-paragraph">二、不锈钢材质分级选用<br>常规自来水选用304不锈钢膜片与壳体，耐自来水余氯轻微腐蚀；水源含轻度酸碱、地下水矿化度高时升级316L不锈钢，降低锈蚀结垢速度，减少堵塞诱因。<br>膜片表面镜面抛光处理，水垢、铁锈难以附着，从源头缓解堵塞问题。</p>



<p class="wp-block-paragraph">三、量程与管网工况匹配<br>结合市政管网常态水压选定量程，日常工作压力处于量程中间段，兼顾测量精度。管网存在水锤冲击点位，选择带抗缓冲结构的型号，避免瞬时高压损伤膜片变形造成淤积堵塞。</p>



<p class="wp-block-paragraph">四、辅助防堵配套选型<br>泥沙含量高的管网，可搭配小型前置过滤器，过滤大颗粒杂质；地表露天管网选用高防护外壳，防止雨水渗入接线部位引发故障。<br>管道震动剧烈的泵房出口，选用抗振型内部传感组件，避免长期震动导致膜片缝隙积垢。</p>



<p class="wp-block-paragraph">五、信号与运维适配选型<br>采用4-20mA标准信号输出，适配管网远程监控系统。仪表结构设计便于快速拆装，日常巡检可直接冲洗膜片表层淤积杂质，降低维护难度。</p>



<p class="wp-block-paragraph">选型总结<br>选型重点为大通径平滑不锈钢膜片、低结垢抛光材质、前置过滤配套，减少管网杂质堵塞问题，让压力变送器长期稳定监测供水管道压力。</p>
<p><a href="https://www.zhanfengdesign.com/9552/">供水管网防堵塞不锈钢压力变送器选型技巧</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></content:encoded>
					
					<wfw:commentRss>https://www.zhanfengdesign.com/9552/feed/</wfw:commentRss>
			<slash:comments>0</slash:comments>
		
		
			</item>
		<item>
		<title>卫生型压力变送器食品制药配液罐选配规范</title>
		<link>https://www.zhanfengdesign.com/9403/</link>
					<comments>https://www.zhanfengdesign.com/9403/#respond</comments>
		
		<dc:creator><![CDATA[jingangxiaohulu3wa]]></dc:creator>
		<pubDate>Mon, 13 Jul 2026 03:01:56 +0000</pubDate>
				<category><![CDATA[压力变送器技术文章]]></category>
		<category><![CDATA[技术文章]]></category>
		<category><![CDATA[压力仪表]]></category>
		<category><![CDATA[压力变送器]]></category>
		<guid isPermaLink="false">https://www.zhanfengdesign.com/?p=9403</guid>

					<description><![CDATA[<p>食品饮料、生物制药行业配液罐、发酵罐、纯 [&#8230;]</p>
<p><a href="https://www.zhanfengdesign.com/9403/">卫生型压力变送器食品制药配液罐选配规范</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></description>
										<content:encoded><![CDATA[
<p class="wp-block-paragraph">食品饮料、生物制药行业配液罐、发酵罐、纯化罐对设备洁净度、无死角、易消毒有硬性标准，常规螺纹压力仪表存在缝隙积料、难以高温灭菌的问题，容易滋生细菌、污染药液原料，不符合GMP洁净车间验收要求。<a href="https://www.zhanfengdesign.com/ylbsq/">卫生型压力变送器</a>采用卡箍无死角结构，适配高温在线灭菌工况，是洁净配液罐体压力在线监测的专用仪表。</p>



<p class="wp-block-paragraph">一、食品制药配液罐工况选配难点</p>



<ol class="wp-block-list">
<li>洁净消毒需求高：罐体需定期CIP/SIP原位清洗、高温蒸汽灭菌，普通仪表不耐高温蒸汽，密封易老化渗漏；</li>



<li>介质易粘附结块：糖浆、蛋白药液、发酵培养基粘稠易附着仪表接触面，缝隙残留会滋生微生物；</li>



<li>生产合规严格：制药车间遵循GMP规范，仪表材质、结构必须无死角、无析出、无污染风险；</li>



<li>工艺压力波动频繁：配料搅拌、输送循环会造成压力小幅震荡，仪表需具备防抖滤波功能；</li>



<li>无二次污染要求：接触介质部件不可析出重金属、塑化剂，保障食品药品生产安全。</li>
</ol>



<p class="wp-block-paragraph">二、卫生结构核心选配标准<br>设备统一采用快装卡盘卡箍连接，无螺纹死角、无藏污缝隙，罐体内接触面平整光滑，清洗液、蒸汽可完全冲刷，杜绝物料残留。传感膜片选用平齐嵌入式设计，与罐体内壁齐平，不会形成凹槽堆积药液，完美适配洁净生产清洗灭菌流程。<br>区别于工业普通压力仪表，整机不含橡胶劣质密封件，全部采用食品级氟橡胶、EPDM密封垫圈，耐受酸碱清洗液、135℃高温蒸汽长期循环灭菌，不易溶胀、不掉碎屑。</p>



<p class="wp-block-paragraph">三、接触介质材质选配规范</p>



<ol class="wp-block-list">
<li>普通饮料、清水配料罐：316L不锈钢膜片与壳体，表面镜面抛光Ra≤0.8μm，不易挂料、便于冲洗；</li>



<li>酸性果汁、弱腐蚀药液配液罐：升级316L LEP电解抛光材质，抗微量有机酸腐蚀；</li>



<li>强腐蚀制药溶媒、含氯清洗工况：可选PTFE包覆卫生膜片，杜绝介质腐蚀金属表面。<br>所有金属材质均提供材质证明文件，满足药厂GMP审计、食品厂质检溯源要求。</li>
</ol>



<p class="wp-block-paragraph">四、温压量程适配选型要点</p>



<ol class="wp-block-list">
<li>量程预留余量：配液罐多为微压常压工况，按照罐体最高工作压力增加20%过载余量，常用0–0.6MPa、0–1.0MPa规格；</li>



<li>灭菌温度适配：标准机型耐受介质温度-20℃～120℃，支持短时135℃高温SIP蒸汽灭菌；长期高温灭菌场景选用耐高温填充液型号，防止内部硅油汽化产生零点漂移；</li>



<li>精度分级：制药配料计量、发酵罐压力精准控制选用0.25级高精度；食品普通工艺监控选用0.5级标准精度，降低采购成本。仪表内置可调阻尼，过滤搅拌循环带来的压力跳变，数值输出平稳。</li>
</ol>



<p class="wp-block-paragraph">五、防护等级与洁净环境适配<br>洁净车间多高湿、频繁水汽熏蒸，仪表外壳防护等级不低于IP67，整机防水防凝露，冲洗设备时清水不会渗入接线腔体。外壳采用拉丝不锈钢一体成型，无拼接缝隙，车间喷淋清洗无进水隐患，不易积灰积污，日常擦拭维护简单。</p>



<p class="wp-block-paragraph">六、信号输出与洁净自控配套<br>标配二线制4–20mA+HART协议，可接入洁净区PLC、中控系统，实时采集罐内压力，联动进料泵、泄压阀、清洗程序自动运行。制药智慧车间可增加RS485 Modbus通讯，多台配液罐仪表组网，远程记录压力曲线，满足生产数据留存追溯要求。<br>洁净防爆车间可选本安防爆型号，防爆等级Ex ia IIB T6，适配酒精、有机溶剂配液高危洁净区域。</p>



<p class="wp-block-paragraph">七、卡箍安装规范要求</p>



<ol class="wp-block-list">
<li>卡盘规格匹配罐体标准卫生接口，DN25、DN40、DN50为制药配液罐通用尺寸，拆装便捷，无需焊接改造罐体；</li>



<li>安装位置选罐体侧面平稳区域，远离搅拌桨、进料喷淋口，减少流体冲击造成压力波动；</li>



<li>卡箍均匀紧固，密封垫圈居中无偏移，灭菌时避免蒸汽泄漏；安装完成后做密封性试压，无渗漏方可投入生产。</li>
</ol>



<p class="wp-block-paragraph">八、洁净运维保养规范<br>每次罐体CIP清洗可同步冲洗仪表膜片，平整光滑表面无需单独拆卸清理；每季度核对零点与量程精度，消除长期高温灭菌带来的轻微偏移；年度更换老化密封垫圈，防止清洗液渗入内部损坏传感芯体。整体无复杂机械结构，洁净车间运维工作量极低。</p>



<p class="wp-block-paragraph">九、选配总结<br>食品制药配液罐压力仪表选配核心围绕卫生无死角、耐高温灭菌、食品级材质、GMP合规四大要点。平整卡箍式卫生结构从根源解决洁净罐体积料、难消毒、污染风险等痛点，监测稳定、拆装清洗便捷，完全满足食品、医药洁净车间标准化生产管控需求。</p>
<p><a href="https://www.zhanfengdesign.com/9403/">卫生型压力变送器食品制药配液罐选配规范</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></content:encoded>
					
					<wfw:commentRss>https://www.zhanfengdesign.com/9403/feed/</wfw:commentRss>
			<slash:comments>0</slash:comments>
		
		
			</item>
		<item>
		<title>压力变送器选型参考要素，介质与管道储罐现场工况匹配梳理</title>
		<link>https://www.zhanfengdesign.com/9162/</link>
					<comments>https://www.zhanfengdesign.com/9162/#respond</comments>
		
		<dc:creator><![CDATA[jingangxiaohulu3wa]]></dc:creator>
		<pubDate>Wed, 24 Jun 2026 14:28:16 +0000</pubDate>
				<category><![CDATA[压力变送器技术文章]]></category>
		<category><![CDATA[技术文章]]></category>
		<category><![CDATA[压力仪表]]></category>
		<category><![CDATA[压力变送器]]></category>
		<guid isPermaLink="false">https://www.zhanfengdesign.com/?p=9162</guid>

					<description><![CDATA[<p>一、介质特性核心选型要素 二、测量类型区 [&#8230;]</p>
<p><a href="https://www.zhanfengdesign.com/9162/">压力变送器选型参考要素，介质与管道储罐现场工况匹配梳理</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></description>
										<content:encoded><![CDATA[
<p class="wp-block-paragraph">一、介质特性核心选型要素</p>



<ol class="wp-block-list">
<li>介质腐蚀程度与传感膜片材质匹配<br>膜片直接接触被测介质，是防腐关键部件，按腐蚀等级分级选用：<br>1）中性介质（清水、压缩空气、柴油、润滑油）：标准 316L 不锈钢膜片，通用性强，成本适中；<br>2）弱酸碱、轻度盐雾、低浓度化工废水：316L 衬四氟膜片，提升抗腐蚀能力；<br>3）浓酸碱、氯化物、电镀废液、强腐蚀溶剂：哈氏合金 C、钽金属膜片，适配强腐蚀工况；<br>4）超高氧化性介质，特种金属膜片仍无法长期耐受时，选用全四氟隔离隔膜结构。</li>



<li>介质粘稠、结晶、易堵塞特性<br>1）低粘度洁净流体、干燥气体：普通螺纹直装变送器，无额外隔离结构；<br>2）重油、树脂、饱和盐溶液、易结晶物料：采用隔膜远传法兰式变送器，加长隔离膜盒，阻隔介质堵塞引压通道，可配套吹扫阀定期清洁膜片；<br>3）高固含、硬质颗粒、长纤维浆料：极易磨损、淤堵膜片与引压口，若无持续吹扫维护条件，不推荐常规<a href="https://www.zhanfengdesign.com/ylbsq/">压力变送器</a>。</li>



<li>介质温度适配，区分填充液与结构<br>1）常温介质（-20℃～100℃）：标准甲基硅油填充隔膜，普通直装螺纹结构；<br>2）高温蒸汽、导热油管路（100℃～350℃）：选用高温苯基硅油隔膜变送器，蒸汽管道需配套冷凝弯隔离高温介质；<br>3）低温冷媒、室外严寒工况（-60℃～0℃）：低温专用防冻硅油，避免低温下填充液粘度飙升造成零点漂移。</li>



<li>易燃易爆挥发性介质<br>汽油、甲醇、液化石油气、锂电电解液等危化介质管路 / 储罐，整机选用本安防爆型压力变送器，配套屏蔽防爆电缆，符合现场防爆分区电气规范。</li>
</ol>



<p class="wp-block-paragraph">二、测量类型区分选型（表压 / 绝压 / 差压 / 密封表压）<br>1.表压变送器：测相对大气压压力，适用常压管道、储罐、水泵、暖通风压，工业最常用；<br>2.绝压变送器：以绝对真空为基准，适用真空机组、精馏负压罐体、低气压精密工艺；<br>3.差压变送器：测量两点压力差值，适用流量孔板、液位双法兰、过滤器压差监测；<br>4.密封表压变送器：隔绝大气湿气，适用野外低温、高湿、高粉尘露天密闭设备。</p>



<p class="wp-block-paragraph">三、安装结构形式工况匹配</p>



<ol class="wp-block-list">
<li>螺纹直装型（M20×1.5、1/2NPT）<br>适配：洁净无结晶常温气体、清水、轻质油品管道，安装便捷、体积小巧；<br>局限：粘稠、高温、腐蚀介质易堵塞引压孔，不适用于强腐蚀工况。</li>



<li>法兰隔膜远传型<br>适配：高温、粘稠、结晶、强腐蚀介质管线与储罐，隔离膜片隔绝介质与传感芯体，避免堵塞腐蚀；<br>局限：配备毛细管，施工工序多，需管控弯折、高温传导问题。</li>



<li>卫生卡箍型（食品制药专用）<br>适配：糖浆、药液、纯化水、发酵罐，卡箍快拆无死角，支持高温清洗、消毒；<br>局限：仅适用于低压洁净工艺，成本高于普通工业款。</li>
</ol>



<p class="wp-block-paragraph">四、量程、压力等级选型规则<br>1.常规稳定工况：工作压力控制在量程 30%～70% 区间，测量精度最优；选型预留 20% 超压安全余量，抵御水锤、瞬时冲击压力；<br>2.微压工况（风机风压、炉膛负压）：微压专用芯体，低压力段灵敏度更高；<br>3.中高压管道、压力容器：高压芯体搭配 PN25/PN40 高压法兰 / 螺纹，耐受瞬时冲击；<br>4.真空负压设备：专用负压 / 绝压量程，杜绝超负压损坏传感芯体。</p>



<p class="wp-block-paragraph">五、温度、震动、户外环境工况适配</p>



<ol class="wp-block-list">
<li>环境温度<br>1）室内恒温厂房：标准 IP65 防护表头即可；<br>2）夏季暴晒露天管线：加装遮阳防雨仪表箱，阻隔高温直射；<br>3）北方冬季室外管路：选用低温适配仪表，隔膜配套保温护套，防止填充液凝固。</li>



<li>管道震动工况（泵、空压机、风机出口）<br>泵体、压缩机高频震动管路，必须配套减震缓冲器 + 减震支架，削弱振动造成数值持续波动；优先选用抗震动加固芯体变送器。</li>



<li>电磁干扰环境<br>变频器、高压电机周边动力管线，仪表线缆单独穿管敷设，采用双层屏蔽电缆并可靠接地，避免信号漂移紊乱。</li>
</ol>



<p class="wp-block-paragraph">六、信号输出与智能功能配套选型<br>1.基础 PLC 自控、普通二次数显：标准 4-20mA 模拟信号输出；<br>2.远程调试、中控智能管理：叠加 HART 协议，手操器远程修改量程、零点、迁移参数；<br>3.多设备组网、数字化平台：RS485 Modbus 数字通讯变送器；<br>4.高低压力联锁报警：可配套带继电器开关量输出型号。</p>



<p class="wp-block-paragraph">七、防爆、防护等级配置<br>1.普通无危化厂房、给排水管线：IP65 标准防护通用型；<br>2.化工、油库、锂电防爆车间：本安 / 隔爆防爆等级整机，防爆认证匹配现场分区；<br>3.雨水直淋、水下、高粉尘露天点位：IP67/IP68 高防护一体式变送器。</p>



<p class="wp-block-paragraph">八、配套辅件匹配梳理<br>1.冷凝弯：高温蒸汽管路标配，隔绝高温介质保护变送器芯体；<br>2.减震缓冲器：泵、空压机震动管线消除脉冲压力；<br>3.吹扫阀门：粘稠结晶介质隔膜定期清洁膜片；<br>4.隔热套管：高温工况毛细管防护，阻隔热量传导；<br>5.根部截止阀：检修变送器无需停机排空管线介质；<br>6.遮阳防雨箱：室外管道表头防护。</p>



<p class="wp-block-paragraph">九、工况适配汇总<br>适配场景<br>给排水管网、暖通风压、油气输送管线、化工反应储罐、电厂蒸汽管道、食品制药洁净工艺、真空负压设备；需要连续压力远传监测，介质涵盖清水、油品、酸碱、高温蒸汽、粘稠结晶物料，可通过螺纹、法兰、卫生卡箍多种结构适配。<br>不适配场景<br>含大量硬质颗粒、长纤维浆料且无吹扫维护；持续超高温无适配高温填充液；剧烈水锤冲击无缓冲装置；狭小设备无法安装隔离隔膜且介质易堵塞引压口。</p>
<p><a href="https://www.zhanfengdesign.com/9162/">压力变送器选型参考要素，介质与管道储罐现场工况匹配梳理</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></content:encoded>
					
					<wfw:commentRss>https://www.zhanfengdesign.com/9162/feed/</wfw:commentRss>
			<slash:comments>0</slash:comments>
		
		
			</item>
		<item>
		<title>压力变送器引起误差的原因与处理</title>
		<link>https://www.zhanfengdesign.com/3016/</link>
		
		<dc:creator><![CDATA[jingangxiaohulu3wa]]></dc:creator>
		<pubDate>Sat, 06 Jul 2024 11:08:57 +0000</pubDate>
				<category><![CDATA[压力变送器技术文章]]></category>
		<category><![CDATA[技术文章]]></category>
		<category><![CDATA[压力仪表]]></category>
		<category><![CDATA[压力变送器]]></category>
		<guid isPermaLink="false"></guid>

					<description><![CDATA[<p>压力变送器和压力传感器一般通过导压管来测 [&#8230;]</p>
<p><a href="https://www.zhanfengdesign.com/3016/">压力变送器引起误差的原因与处理</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></description>
										<content:encoded><![CDATA[<p>压力变送器和压力传感器一般通过导压管来测量压力，流程工艺管道中的压力通过导压管来进行传输，这这个过程中，可能出现的误差有：</p>
<p>1.导压管和流程工艺管道连接不紧密，导致管道中的气体或液体出线泄漏。</p>
<p>2.采用洁净剂时，出线磨损损失。</p>
<p>3.三种原因导致的压头误差：液体管道中有气体、气体管道中有液体、两边导压管之间温差引起的密度不同。</p>
<p>&nbsp;</p>
<p>根据以上原因，减少<a href="https://www.zhanfengdesign.com/ylbsq/">压力变送器</a>误差的解决办法如下：</p>
<p>1.注意导压管与工艺管道连接的紧密性。</p>
<p>2.采用洁净剂时，洁净剂连接处应靠近工艺管道取压口，洁净剂所经过的管路，其长度和口径应相同，应避免洁净剂通过变送器。</p>
<p>3.在条件允许的情况下，使导压管尽可能短。</p>
<p>4.当测量液体或蒸汽时，导压管向上连接到工艺管道，其斜度应不小于1/12。</p>
<p>5.当测量气体时，导压管向下连接到工艺管道，斜度应不小于1/12。</p>
<p>6.充满液体的导压管中应无气体存在。</p>
<p>7.为避免磨擦影响，导压管的口径应足够大。</p>
<p>8.液体导压管道的布设要避免中间出现高点，气体导压管的布设要避免中间出现低点。</p>
<p>9.两导压管之间应保持相同温度。</p>
<p>10.如果使用了隔离液，要保持两边导压管的液体要相同。</p>
<p><a href="https://www.zhanfengdesign.com/3016/">压力变送器引起误差的原因与处理</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>压力变送器故障原因及处理</title>
		<link>https://www.zhanfengdesign.com/3015/</link>
		
		<dc:creator><![CDATA[jingangxiaohulu3wa]]></dc:creator>
		<pubDate>Sat, 06 Jul 2024 11:07:52 +0000</pubDate>
				<category><![CDATA[压力变送器技术文章]]></category>
		<category><![CDATA[技术文章]]></category>
		<category><![CDATA[压力仪表]]></category>
		<category><![CDATA[压力变送器]]></category>
		<guid isPermaLink="false"></guid>

					<description><![CDATA[<p>变送器是自控系统的一个重要组成部分，压力 [&#8230;]</p>
<p><a href="https://www.zhanfengdesign.com/3015/">压力变送器故障原因及处理</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></description>
										<content:encoded><![CDATA[<p>变送器是自控系统的一个重要组成部分，压力变送器主要用于工业过程压力参数的测量和控制，其在石油、化工、电力等领域的应用十分广泛。压力变送器的种类繁多，根据工作原理、用途的不同有不同的分类方式。<a href="https://www.zhanfengdesign.com/ylbsq/">压力变送器</a>主要用于压力的远程显示和控制，其常在高温、低压、腐蚀、振动等环境下工作，出现故障的几率较大，因此对压力变送器的影响因素、常见故障等研究是十分有意义的。</p>
<p>&nbsp;</p>
<p>1、压力变送器常见类型</p>
<p>压力变送器就是能够将压力变量转化为标准输出信号的仪表,压力变量与输出信号间存在一定的函数关系。根据不同的工作原理可将压力变送器分为以下几种：</p>
<p>（1）压阻式变送器。</p>
<p>压阻式变送器是将压力作用到膜片的前表面，在压力作用下膜片会出现一定的形变，感压膜片的背面印有厚膜电阻，进而形成一个惠斯通电桥，在压阻效应下，电桥会产生相应的电压信号，该信号与激励电压成正比例关系。</p>
<p>（2）压电式变送器。</p>
<p>压电式变送器是利用正压电效应研制出来的,正高压电效应就是将一定的外力作用于电解质使其发生变形,电解质内部会出现极化现象,并且在其两个表面会产生正负不同的电荷,外力停止作用时，电解质又恢复到不带电的状态。电荷的极性会随着作用力方向的改变而改变。在电解质极性方向施加电场，电解质也会发生变形，撤销后电解质的形变消失，这就是逆压电效应。</p>
<p>（3）应变式变送器。</p>
<p>采用特殊的粘合剂将应变片粘合在一起进而产生力学应变，在机体受力发生变化时，电阻应变片也会随之出现一定的形变，进而影响到阻值的大小，电阻上的电压发生改变。但是此种情况下阻值的变化较小，通常情况下组成应变电桥，在仪表放大器的作用下变大，最后传输到处理线路显示或执行机构。</p>
<p>（4）电容式变送器。</p>
<p>电容式变送器分电动和气动两类，前者的标准化输入信号为直流信号，后者输出信号为气体压力。待测介质的两种压力分别输入高、低两压力室，作用于敏感元件的两侧隔离膜片上。测量膜片与两侧绝缘片上的电极组成电容器，在两侧压力大小不同的情况下，模块会产生位移，两侧电流大小不同，在震荡和调节作用下，形成电流、电压或者数字输出信号。</p>
<p>&nbsp;</p>
<p>2、压力变送器工作原理</p>
<p>模块电路、显示表头、测压元件传感器、表壳等共同组成了压力变送器。来自两侧导压管的压力差会作用在变送器传感器量测的膜片上，测量元件能够将接受的压力信号转变成标准的电流电压信号，并将信号发送至报警仪、记录仪和调节器，进而对其进行二次测量。</p>
<p>&nbsp;</p>
<p>3、压力变送器的常见故障</p>
<p>压力变送器在使用过程中难免出现各种各样的故障，其影响因素众多，例如压力变送器内隔片与传感原件间存在灌充液漏，零点和量程偏移、输出不稳定等都会导致压力变送器精度下降甚至发生损坏；天气因素也会对变送器造成影响，如雷击会损坏变送器膜盒的电路、导致无法通讯；潮湿的环境会损坏线路；变送器量程选择不合理会造成感压元件不可逆的变形。以下介绍几种常见的故障类型：</p>
<p>（1）线路故障。</p>
<p>当出现线路故障时，计算机显示数值出现异常，将变送器接线盒打开，检查线路是否存在虚接、短接或者断接的现象，在采用测电源、摇绝缘以及量电阻等方法排查故障。</p>
<p>（2）变频干扰</p>
<p>。在进行布线时，多种信号线之间互相干扰，尤其是在动力线与信号线串在同一管道中产生的干扰作用更为严重，此种情况下会导致变送器不通讯甚至致使错误。可以通过增大仪表电缆与动力电缆槽架距离的方式来避免此类错误操作。</p>
<p>（3）引压管故障。</p>
<p>引压管故障通常有引压管堵塞、引压管漏气、引压管积液三种故障类型，引压堵塞一般是由排放不及时或者介质脏、粘等导致的；引压管漏气是由变送器接电、截止阀等附件较多，增加了泄露点；引压管积液通常是由于气体取压方式不合理或者引压管安装错误造成的，引压管积液会影响测量精度。</p>
<p>（4）电信号传输故障</p>
<p>压力变送器若使用或维护不当极易导致电信号的传输故障，例如为了节省时间将变送器放在被测设备附近，导致信号传输距离过远，信号就会出现干扰或衰减现象，此时要根据需要增加电缆线的截面积。</p>
<p>&nbsp;</p>
<p>4、压力变送器故障处理</p>
<p>4.1　输出信号为零</p>
<p>当压力变送器出现压力为零的现象时，可以从以下几个方面进行处理：首先检查管道内是否存在压力，仪表是否正常供电，之后检查是否存在电源极性接反的现象，最后检查电子线路板、感压膜头、变送器电源电压等。</p>
<p>4.2　加压力无反应</p>
<p>若加压力无反应则要检查取压管的阀门是否正常，变送器保护功能跳线开关是否正常，取压管是否堵塞，检查白送器零点和量程，更换传感膜头等。</p>
<p>4.3　压力变量读数偏差</p>
<p>压力变送器出现压力读数明显偏高或偏低的现象时，首先检查取压管路是否存在泄漏现象，再检查取压管上的阀门，对传感器进行微调，若还存在问题，更换新的传感膜头。</p>
<p>4.4　压力变量读数不稳定</p>
<p>该问题可通过隔离外界干扰源、检查导压管是否泄漏、管道是否存在杂物、检查隔离膜片时候出现服饰或变形、检查感压膜头等方法来排查。</p>
<p>&nbsp;</p>
<p>5、结语</p>
<p>目前压力传感器的使用十分广泛，无论是国产变送器还是进口变送器，在使用过程中由于工作环境、人为操作不当或者自身原因都会出现各种故障，因此我们不仅要按照说明书的标准规范进行操作，还要掌握正确的故障判断、养护和维修知识，这样才能保证压力传感器的使用寿命和测量精度。</p>
<p><a href="https://www.zhanfengdesign.com/3015/">压力变送器故障原因及处理</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>压力变送器的维护与保养</title>
		<link>https://www.zhanfengdesign.com/3014/</link>
		
		<dc:creator><![CDATA[jingangxiaohulu3wa]]></dc:creator>
		<pubDate>Wed, 26 Jun 2024 10:00:25 +0000</pubDate>
				<category><![CDATA[压力变送器技术文章]]></category>
		<category><![CDATA[技术文章]]></category>
		<category><![CDATA[压力仪表]]></category>
		<category><![CDATA[压力变送器]]></category>
		<guid isPermaLink="false"></guid>

					<description><![CDATA[<p>压力变送器用于测量液体、气体或蒸汽的液位 [&#8230;]</p>
<p><a href="https://www.zhanfengdesign.com/3014/">压力变送器的维护与保养</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></description>
										<content:encoded><![CDATA[<p>压力变送器用于测量液体、气体或蒸汽的液位、密度和压力，然后将压力信号转变成4-20mADC信号输出。主要有电容式压力变送器和扩散硅压力变送器，陶瓷压力变送器，应变式压力变送器等。介质压力直接作用于敏感膜片上，分布于敏感膜片上的电阻组成的惠斯通电桥，利用压阻效应实现了压力量向电信号的转换，通过电子线路将敏感元件产生的毫伏信号放大为工业标准信号。</p>
<p>&nbsp;</p>
<p>日常维护</p>
<p>1、检查安装孔的尺寸</p>
<p>如果安装孔的尺寸不合适，传感器在安装过程中，其螺纹部分就很容易受到磨损。这不仅会影响设备的密封性能，而且使压力传感器不能充分发挥作用，甚至还可能产生安全隐患。只有合适的安装孔才能够避免螺纹的磨损(螺纹工业标准1/2-20 UNF 2B)，通常可以采用安装孔测量仪对安装孔进行检测，以做出适当的调整。</p>
<p>&nbsp;</p>
<p>2、保持安装孔的清洁</p>
<p>保持安装孔的清洁并防止熔料堵塞对保证设备的正常运行来说十分重要。在挤出机被清洁之前，所有的压力传感器都应该从机筒上拆除以避免损坏。在拆除传感器时，熔料有可能流入到安装孔中并硬化，如果这些残余的熔料没有被去除，当再次安装传感器时就可能造成其顶部受损。清洁工具包能够将这些熔料残余物去除。然而，重复的清洁过程有可能加深安装孔对传感器造成的损坏。如果这种情况发生，就应当采取措施来升高传感器在安装孔中的位置。</p>
<p>&nbsp;</p>
<p>3、选择恰当的位置</p>
<p>当1151/3351DP<a href="https://www.zhanfengdesign.com/ylbsq/">压力变送器</a>的安装位置太靠近生产线的上游时，未熔融的物料可能会磨损传感器的顶部；如果传感器被安装在太靠后的位置，在传感器和螺杆行程之间可能会产生熔融物料的停滞区，熔料在那里有可能产生降解，压力信号也可能传递失真；如果传感器过于深入机筒，螺杆有可能在旋转过程中触碰到传感器的顶部而造成其损坏。一般来说，传感器可以位于滤网前面的机筒上、熔体泵的前后或者模具中。</p>
<p>&nbsp;</p>
<p>4、仔细清洁</p>
<p>在使用钢丝刷或者特殊化合物对挤出机机筒进行清洁前，应该将所有的传感器都拆卸下来。因为这两种清洁方式都可能会造成传感器的震动膜受损。当机筒被加热时，也应该将传感器拆卸下来并使用不会产生磨损的软布来擦拭其顶部，同时传感器的孔洞也需要用清洁的钻孔机和导套清理干净。</p>
<p>&nbsp;</p>
<p>5、保持干燥</p>
<p>尽管1151/3351DP压力变送器传感器的电路设计能够经受苛刻的挤出加工环境，但是多数传感器也不能绝对防水，在潮湿的环境下也不利于正常运行。因此，需要保证挤出机机筒的水冷装置中的水不会渗漏，否则会对传感器造成不利影响。如果传感器不得不暴露在水中或潮湿的环境下，就要选择具有极强防水性的特殊传感器。</p>
<p>&nbsp;</p>
<p>6、避免低温干扰</p>
<p>在挤出生产过程中，对于塑料原料而言，从固体到熔融状态应当具有充足的“浸透时间”。如果挤出机在开始进行生产前还没有达到操作温度，那么传感器和挤出机都会受到一定程度的损坏。另外，如果传感器从冷的挤出机上被拆除，材料就可能粘附在传感器顶部引起震动膜的损坏。因此，在拆除传感器之前，应确认机筒的温度足够高，机筒内部的物料处于软化状态下。</p>
<p>&nbsp;</p>
<p>7、防止压力过载</p>
<p>即使1151/3351DP压力变送器测压范围的过载设计最高能够达到50%(超出最大量程的比率)，从设备运行的安全角度考虑也应该尽量避免冒险，最好选择被测压力处于量程范围之内的传感器。在通常情况下，所选传感器的最佳量程应该是被测压力的2倍，这样即使挤出机在极高的压力下运行，也能避免压力传感器受到损坏。 压力变送器要求每周检查一次，每个月检验一次，主要是清除仪器内的灰尘，对电器元件认真检查，对输出的电流值要经常校对，压力变送器内部是弱电，一定要同外界强电隔开。</p>
<p><a href="https://www.zhanfengdesign.com/3014/">压力变送器的维护与保养</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>压力变送器的工作原理</title>
		<link>https://www.zhanfengdesign.com/3013/</link>
		
		<dc:creator><![CDATA[jingangxiaohulu3wa]]></dc:creator>
		<pubDate>Wed, 26 Jun 2024 09:57:59 +0000</pubDate>
				<category><![CDATA[压力变送器技术文章]]></category>
		<category><![CDATA[技术文章]]></category>
		<category><![CDATA[压力仪表]]></category>
		<category><![CDATA[压力变送器]]></category>
		<guid isPermaLink="false"></guid>

					<description><![CDATA[<p>压力变送器是一种在工业生产控制过程中被广 [&#8230;]</p>
<p><a href="https://www.zhanfengdesign.com/3013/">压力变送器的工作原理</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></description>
										<content:encoded><![CDATA[<p>压力变送器是一种在工业生产控制过程中被广泛使用的压力参数监测装置，应用于石油化工、水利水电、铁路交通等诸多领域。它能够用于连续精确地测量气体、液体及蒸汽的压力、差压、绝对压力、液位等工艺参数，并将被测信号通过其转换功能转换为4~20mA的HART信号输出，以供其他控制调节仪表和DCS分散控制系统等使用。</p>
<p>&nbsp;</p>
<p>由于<a href="https://www.zhanfengdesign.com/ylbsq/">压力变送器</a>具有精度高、漂移小、长期稳定性好、功能丰富等优点，所以是工业生产实现现代化、自动化的关键部件。因此，保证智能压力变送器的可靠性就显得尤为重要，其可靠性的高低对于整个系统生产过程无故障运行来说具有重大影响。</p>
<p><img decoding="async" title="1719367184150514.png" src="/static/upload/image/20240626/1719367184150514.png" alt="_0240626095449.png/" /></p>
<p>&nbsp;</p>
<p>压力变送器工作原理如图1所示。图1中主要包含有δ室传感器、传感器激励与信号调理电路、A/D转换电路、微处理器、D/A转换电路、HART通信、显示电路等。其中，δ室传感器是关键元件。由于要检测传感器本体的温度变化，所以将高精度的温度传感器嵌于δ室的正压端，即构成压力温度复合传感器。当外界压力作用于δ室的隔离膜片上时，通过灌冲硅油的传递，可以将压力的变化传递到位于中心的测量膜片上，使其产生微小的位移（最大为0.08mm），其位移距离与所受到的压力成正比。中心测量膜片的位移变化，会引起两固定电容极板的电容量发生改变，通过电容量的变化即可检测出压力的变化。</p>
<p><a href="https://www.zhanfengdesign.com/3013/">压力变送器的工作原理</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>压力变送器与差压变送器的区别</title>
		<link>https://www.zhanfengdesign.com/2849/</link>
		
		<dc:creator><![CDATA[jingangxiaohulu3wa]]></dc:creator>
		<pubDate>Sat, 29 Jul 2023 10:14:01 +0000</pubDate>
				<category><![CDATA[压力变送器技术文章]]></category>
		<category><![CDATA[技术文章]]></category>
		<category><![CDATA[压力仪表]]></category>
		<category><![CDATA[压力变送器]]></category>
		<guid isPermaLink="false"></guid>

					<description><![CDATA[<p>压力变送器与差压变送器，名称听起来名称十 [&#8230;]</p>
<p><a href="https://www.zhanfengdesign.com/2849/">压力变送器与差压变送器的区别</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></description>
										<content:encoded><![CDATA[<p>压力变送器与差压变送器，名称听起来名称十分相似，但它们不是一种产品，很多人也知道它们是不同的，可是又说不出到底差别在哪里，今天我们就来专门给大家讲解一下，它们之间的差别，帮助大家快速了解<a href="https://www.zhanfengdesign.com/ylbsq/">压力变送器</a>和<a href="https://www.zhanfengdesign.com/cybsq/">差压变送器</a>的区别。</p>
<p>&nbsp;</p>
<p>差压变送器是针对气体和液体压强设计制造的，单位是帕斯卡，而压力变送器也是针对气体与液体的，不过它的单位是牛顿或者千克，虽然针对同样的介质类型，可它们的计量单位是不同的，所以这也是区分二者的外在标准之一。</p>
<p>&nbsp;</p>
<p>差压变送器能够测量两个容器间的气体或液体的压强，这个量是一个相对的数值，而压力变送器则是单个容器内的气压或者液压，这个数值则是一个绝对的量了，选择两种产品时，也要参考这个标准，结合自己的行业属性选择对应的产品类型。</p>
<p>&nbsp;</p>
<p>从使用上区分，差压变送器的输入管口有两个，分别是用来引入不同测量样品的，这样可以同时获得两个不同样品的压差，而压力变送器则只有一个管口，只能单一测量一个样品的羞压。</p>
<p>&nbsp;</p>
<p>了解压力变送器与差压变送器的区别，可以帮助您选择正确合理地选择产品类型，您也可以向生产厂家咨询，获得更多相关产品的知识，帮您更多地减少产品选型中的误区，更加有效。</p>
<p><a href="https://www.zhanfengdesign.com/2849/">压力变送器与差压变送器的区别</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>压力变送器选型考虑因素</title>
		<link>https://www.zhanfengdesign.com/2848/</link>
		
		<dc:creator><![CDATA[jingangxiaohulu3wa]]></dc:creator>
		<pubDate>Sat, 29 Jul 2023 09:55:12 +0000</pubDate>
				<category><![CDATA[压力变送器技术文章]]></category>
		<category><![CDATA[技术文章]]></category>
		<category><![CDATA[压力仪表]]></category>
		<category><![CDATA[压力变送器]]></category>
		<guid isPermaLink="false"></guid>

					<description><![CDATA[<p>压力变送器是工业实践中最为常用的现场仪表 [&#8230;]</p>
<p><a href="https://www.zhanfengdesign.com/2848/">压力变送器选型考虑因素</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></description>
										<content:encoded><![CDATA[<p>压力变送器是工业实践中最为常用的现场仪表，在电气设备中压力变送器起着类似于传感器的功能，它能将测压元件传感器感受到的气体、液体等物理压力参数转变成标准的电信号（如4~20mA.DC等），以供给指示报警仪、记录仪、调节器等二次仪表进行测量、指示和过程调节。</p>
<p><img decoding="async" title="1690595747198147.jpg" src="/static/upload/image/20230729/1690595747198147.jpg" alt="tup1.jpg/" /></p>
<p><a href="https://www.zhanfengdesign.com/ylbsq/">压力变送器</a>广泛应用于各种工业自控环境。由于压力变送器是直接与被测介质接触的现场仪表，常常在高温、低温、腐蚀、振动、冲击等环境中工作，因此压力变送器选型时，除了要考虑测量范围与精度等一般仪表需要考虑的内容外，工作环境与被测介质等方面也是重要的指标之一。</p>
<p>总体而言，压力变送器的选型，以下10个方面要注意：</p>
<p>&nbsp;</p>
<p>一、压力变送器的选型规则</p>
<p>01</p>
<p>据要测量压力的类型。压力类型主要有表压、绝压、差压。</p>
<p>表压是指以大气为基准，小于或大于大气压的压力；</p>
<p>绝压是指以绝对压力零位为基准，高于绝对压力；</p>
<p>差压是指两个压力之间的差值。</p>
<p>&nbsp;</p>
<p>02</p>
<p>根据被测压力量程。一般情况下，实际测量压力按测量范围的80%选取。一般来说，压力变送器压力范围最大值应该达到系统最大压力值的1．5倍。一些水压和过程控制，有压力尖峰或者连续的脉冲，这些尖峰可能会达到最大压力的5倍甚至10倍，造成变送器的损坏。</p>
<p>&nbsp;</p>
<p>03</p>
<p>根据被测介质。按测量介质的不同，可分为干燥气体、气体液体、强腐蚀性液体、黏稠液体、高温气体液体等，根据不同的介质正确选型，有利于延长变送器的使用寿命。</p>
<p>&nbsp;</p>
<p>04</p>
<p>根据系统的最大过载。系统的最大过载应小于变送器的过载保护极限，否则会影响变送器的使用寿命甚至损坏变送器。通常压力变送器的安全过载压力为满量程的2倍。</p>
<p>&nbsp;</p>
<p>05</p>
<p>根据需要的准确度等级。变送器的测量误差按准确度等级进行划分，不同的准确度对应不同的基本误差限（以满量程输出的百分数表示）。实际应用中，根据测量误差的控制要求并本着使用经济的原则进行选择。</p>
<p>&nbsp;</p>
<p>06</p>
<p>根据系统工作温度范围。测量介质温度应处于变送器工作温度范围内，如超温使用，将会产生较大的测量误差并影响变送器的使用寿命。在温度较高的场合，可以考虑选择高温型压力变送器或采取安装冷凝管、散热器等辅助降温措施。</p>
<p>&nbsp;</p>
<p>07</p>
<p>根据测量介质与接触。材质的兼容性在某些测量场合，测量介质具有腐蚀性，此时需选用与测量介质兼容的材料或进行特殊的工艺处理，确保变送器不被损坏。</p>
<p>&nbsp;</p>
<p>08</p>
<p>根据压力接口形式。通常以螺纹连接（M20×1．5）为标准接口形式。</p>
<p>&nbsp;</p>
<p>09</p>
<p>根据供电电源和输出信号。通常压力变送器采用直流电源供电，提供多种输出信号选择，包括4～20mA．DC；、0～5V．DC、1～5V．DC、0～10mA．DC等，可以有232或485数字输出。</p>
<p>&nbsp;</p>
<p>10</p>
<p>根据现场工作环境情况及其他。现场是否存在振动及电磁干扰等，选型时应提供相关信息，以便采取相应处理。</p>
<p>&nbsp;</p>
<p>在选型时，若有需要，电气连接方式也可以根据具体情况予以考虑。</p>
<p><a href="https://www.zhanfengdesign.com/2848/">压力变送器选型考虑因素</a>最先出现在<a href="https://www.zhanfengdesign.com">金湖凯铭仪表</a>。</p>
]]></content:encoded>
					
		
		
			</item>
	</channel>
</rss>
